Turbine flow sensors with threaded connection / Version for HVAC and industrial
型號:Type VT40- Pressure rating up to 50 bar
- 
        The SIKA turbine flow sensor type VT40 is used for flow measurement and dosing in water and water mixtures. The sensor is used in many applications, including: - monitoring of cooling circuits in machine and plant construction
- water treatment
- cleaning processes
- dosing
 The liquid flowing into the turbine flow sensor is divided into partial jets by the blading. These hit the rotor uniformly from different directions and cause it to rotate. The speed of the rotor is now converted into an electrical pulse signal (frequency): The rotor is equipped with magnets, a Hall effect sensor detects the rotational movement. A flow proportional frequency signal (square wave signal) is available. The geometry of the blading and rotor enables the realization of very low start-up values. Series VTH40 VTM40 - Cost optimized version
 - Pressure rating up to 50 bar
 
- 
        Type VTH40 VTM40 Material pipe section Brass Flow range 0.4...25 m³/h (6.7...417 l/min)* Accuracy ±7 % of the measured value between 0.4...3 m³/h 
 ±5 % of the measured value between 3...25 m³/hRepeatability ±0.5 % Signal output From 0.28 m³/h Medium temperature 0...85 °C (non-freezing) Pressure rating PN 10 PN 50 Nominal diameter DN 40 Process connection G 2 male thread, supplementary screwed connection recommended Sensor Hall effect sensor Output signal 
 → Pulse rate / K-factor
 →Resolution
 → Signal shape→ Signal current 
 26.6 pulses/l
 37.6 ml/pulse
 Square wave signal
 NPN open collector
 Max. 19 mAElectrical connection 2 m PVC cable, shielded (Tmax = 75 °C) 4 pin plug connector M12 x 1 Power supply 10...30 VDC 
 optional 4.5. 26.5 VDC6.5...24 VDC 
 short circuit proof and reverse polarity protectedDegree of protection IP54 Max. particle size in the medium < 0.63 mm Integrated screen filter Flat filter, mesh size 0.63 mm * not suitable for continuous operation 

 
 
 
 
 
             
    